Skip to main content

Load-break switch 12 kV, 630 A | FLN36-12D/630-20, FLRN36-12D/T125-31.5

Load-break switch  12 kV, 630 A | FLN36-12D/630-20, FLRN36-12D/T125-31.5

    Skype : mark2002719   emal : mark2002719@gmail.com



FLN36-12D/630-20 SF6 Switch / FLRN36-12D/T125-31.5 SF6 Switch-fuse Combination

Application: in the system of 50Hz, 12kV for making and breaking of load current, over-load current and short-circuit current to control and protect the circuit and transformer, etc.
Standards: IEC 60265, IEC 60420

Features:
 Indication of the active contact to show the operation status of the switch. 
 High insulation level. 
 Fully sealed and reliable operation.

Technical Data:
 Rated voltage(kV): 12
 Rated current(A): FLN36-12D: 630; FLRN36-12D: 125
 Rated frequency(Hz): 50
 Rated short-time withstands current of switch/ Rated continuous time of short-circuit(kA/s): FLN36-12D: 20/3
 Rated short-time withstands current of earthing switch/ Rated continuous time of short-circuit(kA/s): FLN36-12D: 20/2 
 Rated peak withstand current and rated short-circuit making current(kA): FLN36-12D: 50; FLRN36-12D: 125 (anticipated)
 Breaking current of active load(A): FLN36-12D: 630
 5% rated breaking current of active load(A): FLN36-12D: 31.5
 Cable-charging breaking current(A): FLN36-12D: 10
 Breaking capacity of no-load transformer(kVA): 1250
 Breaking transfer current(A): FLRN36-12D: 1700
 Prospective short-circuit breaking current(kA): FLRN36-12D: 50
 1 min power frequency withstands voltage, phase-to-phase, to earth/break(kV): 42/48
 Lighting impulse withstands voltage, phase-to-phase, to earth/break(kV): 75/78
 Mechanical life: 2000
 Rated pressure of SF6 gas (gauge pressure at 20℃) [Mpa]: 0.04~0.05

Comments

Popular posts from this blog

SF6 gas insulated circuit breaker / high-voltage 40.5 kV | LW8

SF6 gas insulated circuit breaker / high-voltage  40.5 kV | LW8 Skype : mark2002719   email : mark2002719@gmail.com LW8 40.5 kV SF6 Circuit Breaker Application: for control and protection of 40.5 kV power system. Ratings: 40.5kV, 2000A Standards: IEC 62271-100 Features:  With CT14 spring operation mechanism.  High breaking capacity.  Secure and reliable operation.  Applicable for frequent operation; easy or free of maintenance. Technical Data: Rated voltage (kV):40.5 Rated current (A): 2000 Rated short-circuit breaking current for Isc: 31.5; 25; 31.5; 25 Rated short-time withstands current/continuous time (kA/s): 31.5/4; 25/4; 31.5/4; 25/4 Rated withstands current (peak): 80; 63; 80; 63 Rated short-circuit making current (peak) (kA): 80; 63; 80; 63 Power frequency withstands voltage for 1min (Breaks) (kV): 95+24; 95; 95; 95 Power frequency withstands voltage for 1min (To earth) (kV): 95; 95; 95; 95 Lighting impulse withstand vol

rccb circuit breaker F364 30ma

F364 30ma  electrical rccb 1.Manufactory Profile: CNC electric Co., Ltd is a professional manufacturer of low voltage electrical producs and materials in China, We specialize in this field for 15 years. As our products quality are stable & reliable, prices are reasonable and service also fine,  most of them sells very good in UK, Iran, Pakistan, India, Bangladesh,Dubai, Thailand, Zambia and so on.  We also have considerable experience on R&D, design and OEM, besides the current products, we also can supply made to meansure products to your sample. You are welcome to call consultations, negotiations.     2.Basic Parameters: Standrad IEC/EN61008 Mode Electro-magnetic type,electronic type Type(wave form of the earth leakage sensed) AC,A Rated current ln 16,25,32,40,63A Poles 2,4P Rated voltage Ue AC240/415 lnsulation voltage Ui 500V Rated frequency 50/60Hz Electrical life 6000t Mechanical life 10000t Fault current inditor