Application: in the system of 50Hz, 40.5kV, for power distribution, circuit control and protection.

Parameters: 
Rated voltage: 40.5kV. 
Rated current: 630-2000A. 
Rated short-circuit breaking current: 25-31.5kA.

Standards: IEC 62271-200

Features:
 Compact design.
 Easy operation and installation.
 Reliable interlock.
 Less Maintenance.

Technical Data:
 Rated voltage (kA): 40.5
 Rated current:
- Rated current of main bus bar (A): 1250 to 2000
- Rated current of matched VCB (A): 1250 to 2000
- 1min power frequency withstands voltage (kV): 95
- Rated thundering withstands voltage (kV): 185
- Power frequency withstands voltage of auxiliary circuit and control circuit (V/1min): 2000
 Rated frequency (Hz): 50
 Rated short circuit breaking current (kA): 20 to 31.5
 Rated short-time withstands current (kA): 20 to 31.5
 Rated short-circuit continuous time (S): 4
 Rated withstands current (peak) [kA]: 50 to 80
 Rated short-circuit making current (kA): 50 to 80
 Rated voltage of control circuit (V):
- DC: 110, 220
- AC: 110, 220
 Protection grade:
- Switchgear enclosure: IP3X
- Inter-chambers (door opened): IP2X

Comments

Popular posts from this blog

SF6 gas insulated circuit breaker / high-voltage 40.5 kV | LW8

SF6 gas insulated circuit breaker / high-voltage  40.5 kV | LW8 Skype : mark2002719   email : mark2002719@gmail.com LW8 40.5 kV SF6 Circuit Breaker Application: for control and protection of 40.5 kV power system. Ratings: 40.5kV, 2000A Standards: IEC 62271-100 Features:  With CT14 spring operation mechanism.  High breaking capacity.  Secure and reliable operation.  Applicable for frequent operation; easy or free of maintenance. Technical Data: Rated voltage (kV):40.5 Rated current (A): 2000 Rated short-circuit breaking current for Isc: 31.5; 25; 31.5; 25 Rated short-time withstands current/continuous time (kA/s): 31.5/4; 25/4; 31.5/4; 25/4 Rated withstands current (peak): 80; 63; 80; 63 Rated short-circuit making current (peak) (kA): 80; 63; 80; 63 Power frequency withstands voltage for 1min (Breaks) (kV): 95+24; 95; 95; 95 Power frequency withstands voltage for 1min (To earth) (kV): 95; 95; 95; 95 Lighting impulse withstand vol

Load-break switch 12 kV, 630 A | FLN36-12D/630-20, FLRN36-12D/T125-31.5

Load-break switch   12 kV, 630 A | FLN36-12D/630-20, FLRN36-12D/T125-31.5     Skype : mark2002719   emal : mark2002719@gmail.com FLN36-12D/630-20 SF6 Switch / FLRN36-12D/T125-31.5 SF6 Switch-fuse Combination Application: in the system of 50Hz, 12kV for making and breaking of load current, over-load current and short-circuit current to control and protect the circuit and transformer, etc. Standards: IEC 60265, IEC 60420 Features:  Indication of the active contact to show the operation status of the switch.   High insulation level.   Fully sealed and reliable operation. Technical Data:  Rated voltage(kV): 12  Rated current(A): FLN36-12D: 630; FLRN36-12D: 125  Rated frequency(Hz): 50  Rated short-time withstands current of switch/ Rated continuous time of short-circuit(kA/s): FLN36-12D: 20/3  Rated short-time withstands current of earthing switch/ Rated continuous time of short-circuit(kA/s): FLN36-12D: 20/2   Rated peak withstand current and rated short-circuit making

earth fault breaker/ID RCCB

ID-I earth fault breaker/ID RCCB 1,Provides protection against earth fault/leakage current and function of isolation High breaking current withstand capacity. 2,Applicable to terminal and pin/fork type busbar connection. 3,Equipped with finger protected connection terminals. 4,Fire resistant plastic parts endures abnormal heating and strong impact. 5,Automatically disconnect the circuit when earth fault/leakage current occurs and exceeds the rated sensitivity Independent of power supply and line voltage, and free from external interference, voltage fluctuation. Technical Data   Mode Electro-magnetic type, electronic type Residual current characteristics A, AC Pole No. 2, 4 Rated making and breaking capacity 630A Rated current(A) 16 25 40 63 80 100A Rated voltage 240/415V AC Rated frequency 50/60Hz Rated residual operating current IΔn(mA) 10, 30, 100, 300, 500 Rated residual non operating current IΔno 0.5IΔn Rated conditional breaking current Inc 6000A Ra